Screenzone Commercial Recessed Air Curtains

Designed to fit above a doorway in a suspended ceiling, the Screenzone recessed air curtains provides a discreet welcoming curtain of warmth for doorways in shops, hotels, offices and commercial premises. Overall energy savings are likely when the heater is sited above a frequently opened external door as the airstream can prevent heat loss.

RAC0603, RAC0604 & RAC1006

  • 3kW, 4.5kW or 6kW rating.
  • Single phase models.
  • Will fit a recess as shallow as 210mm (155mm unit depth plus 55mm free air).
  • Supplied with remote switch HE8407.
  • 3 heat settings.
  • Fan only setting for air circulation.
  • Automatic safety cut-out for thermal overload protection.
  • Supplied with white grille.

RAC1306, RAC1309, RAC1312, RAC1509, RAC1512, RAC1514 & RAC1516

  • 6kW, 9kW, 12kW, 14kW or 16kW rating
  • Will fit a recess as shallow as 230mm (175mm unit depth plus 55mm free air)
  • Energy efficient brushless motor.
  • Supplied with HE8408 remote switch.
  • Multiple heaters can be controlled from one switch.
  • Optional ACMC (Air Curtain Master Controller) and ACTS (Air Curtain Temperature Sensor) available.
  • ACTS must be used in conjunction with ACMC.
  • 2 heat settings, 2 fan speeds with remote switch.
  • 8 heat settings, 8 fan speeds with optional ACMC.
  • Fan only setting for air circulation.
  • Automatic safety cut-out for thermal overload protection.
  • Safety monitoring feature: This feature will detect and display the nature of the fault on the display screen on ACMC controller. If ACMC controller is not used, the LED indicator light located under the heater cover will flash indicating the nature of the fault.
  • Compatible with Building Management Systems.
  • Finished in white.

Dimensions:

Model Depth (mm) Width (mm) Length (mm) Weight (kg)
RAC0603/RAC0604 155 339 634 9.5
RAC1006 155 339 985 13.5
RAC1306/RAC1309/RAC1312 175 339 1350 19.5
RAC1509/RAC1512/RAC1514/RAC1516 175 339 1550 21.0
Model No kW Max. Mounting
Height (m)
Single Phase 3 Phase dBA
RAC0603 3 3.0 *   55
RAC0604 4.5 3.0 *   55
RAC1006 6 3.0 *   57
RAC1306 6 3.4 * * 60
RAC1309 9 3.4 * * 60
RAC1312 12 3.4   * 62
RAC1509 9 3.4   * 62
RAC1512 12 3.4   * 62
RAC1514 14 3.4   * 62
RAC1516 16 3.4   * 62

Note: dBA readings are taken at 3 meters from the heater in a free field environment.